| Plan Review Notes For Permit 03042122 |
| Permit Number |
03042122 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. - BIDET IN MASTER | | | BATH IS NOT VENTED. KITCHEN SINK IS | | | MISLABELED AS LAV. - DISHWASHER SHALL | | | TIE IN UPSTREAM OF TRAP. - WASH MACHINE | | | SHALL TIE IN DOWNSTREAM OF LAUNDRY SINK, | | | (NOT ON L/SINK WASTE ARM, AND REQUIRES A | | | TRAP AND A STANDPIPE. - CLEAN OUT SHALL | | | BE LOCATED 4' ABOVE FINISHED FLOOR ABOVE | | | WASH MACHINE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|