| Plan Review Notes For Permit 03042122 |
| Permit Number |
03042122 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-14 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES FOR | | | CODE COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} SHOW THE LOCATIONS OF THE SERVICE | | | EQUIPMENT ON THE DRAWINGS. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE A #2 PER 250-66 AND CONTINUOUS | | | PER 250-64(C). | | | | | | 3} ADD RECEPTACLE IN THE BREAKFAST AREA | | | PER 201-52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|