Plan Review Notes
Plan Review Notes For Permit 03042121
Permit Number 03042121
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS. CHAPTER
 1, ADMIN. CODE
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES RISER REFLECT
 THE FLOOR PLAN.
 2) NO LOOP PIPING IN MASTER BATH. BIDET
 REQUIRES A TRAP.
 3) W/M REQUIRES A TRAP AND A STANDPIPE.
 4) SHOWER MISSING BATH #2
 5) TUB MISSING BATH #3
 6) IS THE FIXTURE BY THE KITCHEN A BAR
 SINK OR A LAV?
 7) PIPE SIZING MISSING.
 SECTIONS 104.2.1, 802.4, 706.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692