| 2003-07-08 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SUBSURFACE SOIL BORING TEST |
| | REPORT FROM A FL LICENSED SOIL ENGINEER |
| | AS REQUIRED BY CITY AMENDMENTS TO |
| | FBC 1804.2.2. |
| | |
| | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | INDICATE THE IMPORTANCE FACTOR (1.00) & |
| | THE BUILDING CATEGORY ON THE PLANS (II). |
| | THE INTERNAL PRESSURE COEFFICENT DOES |
| | NOT HAVE THE +/- IN FRONT OF IT WHICH |
| | INDICATES POSITIVE AND NEGATIVE PRESSURE |
| | |
| | 5) BECAUSE A FULL BATHROOM IS PROVIDE AT |
| | HABITABLE GRADE LEVEL, ONE OF THE FULL |
| | BATHROOMS IS REQUIRED TO HAVE A DOOR |
| | WITH A 29" CLEAR OPENING. |
| | SEE FBC 11-4.23. |
| | |
| | 6) SOME OF THE VALUES LISTED IN THE |
| | TRUSS ANCHOR SCHEDULE ARE INCORRECT. |
| | PLEASE INDICATE VALUES FROM THE 2003 USP |
| | CATALOG WHICH DO NOT INCLUDE THE ONE- |
| | THIRD INCREASE ON THE STEEL CALCULATIONS |
| | PER FBC 1609.4. |
| | |
| | 7) PLEASE UPDATE THE HUGHES AND SEMCO |
| | CONNECTORS SPECIFIED ON THE SECTIONS ON |
| | A6 TO CURRENT USP CONNECTORS. HUGHES AND |
| | SEMCO WERE PURCHASED BY USP. |
| | |
| | 8) THE CALCULATIONS FOR THE ENERGY |
| | FORM ARE BASED ON CONDITIONED SPACE |
| | AREA WHICH DOES NOT CORRESPOND WITH THE |
| | CONDITIONED AREA LISTED ON THE PLANS. |
| | PLEASE SUBMIT NEW ENERGY CALCULATIONS |
| | WITH THE CORRECT CONDITIONED FLOOR AREA. |
| | |
| | 9)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - CASEMENT WINDOWS |
| | - IN ADDITION TO THE DRAWING FOR THE |
| | GARAGE DOOR THE SBCCI REPORT #9606C IS |
| | REQUIRED. |
| | |
| | 10) THE PRODUCT APPROVAL FOR THE WINDOW |
| | MULLIONS DO NOT MEET THE WINDLOAD |
| | REQUIREMENTS AT THE LIVING ROOM WINDOW. |
| | THE PRODUCT APPROVAL LIMITS THE NUMBER |
| | OF WINDOWS THAT CAN BE MULLED TOGETHER |
| | TO FIVE (5). THE LIVING ROOM WINDOW HAS |
| | SIX (6). SUBMIT A PRODUCT APPROVAL FOR |
| | MULLIONS THAT WILL MEET WINDLOADS FOR |
| | THIS OPENING OR PROVIDE DETAIL ON THE |
| | PLAN FOR AN ENGINEERED MULLION OR A |
| | LINTEL BETWEEN THE TOP AND BOTTOM |
| | WINDOWS. |
| | |
| | 11) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR THE OPTIONAL |
| | BBQ IF IT WILL BE INSTALLED. |
| | |
| | 12) THE NEW SHEETS ARE REQUIRED TO HAVE |
| | THE WET SIGNATURE OF THE ARCHITECT. A |
| | SIGNATURE STAMP IS NOT ACCEPTABLE. |
| | SEE FAC 61G1-16.003 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |