| Plan Review Notes For Permit 03042121 |
| Permit Number |
03042121 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | | FLECT THE FLOOR PLAN. | | | 2) 909.1 WASH MACHINE & LAUNDRY SINK | | | SHALL NOT DRAIN INTO THE HORIZONTAL WET | | | VENT OF THE BATHROOM GROUP. W/M & L/T | | | SHALL TIE IN DOWNSTREAM OF THE BATHROOM | | | GROUP. | | | 3) VERTICAL RISE ON AN ISOMETRIC INDICAT | | | ES A SECOND FLOOR. | | | 4) 905.3 NO HORIZONTAL DRY VENTS. | | | 5) KITCHEN SINK MISLABLED AS LAVS. | | | 6) BIDET NOT VENTED | | | 7) PIPE SIZES MISSING | | | (SEE SHEET ATTACHED TO PERMIT #03041590 | | | FOR AN EXAMPLE OF APPROVED SANT. RISER | | | DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|