Plan Review Notes
Plan Review Notes For Permit 03042121
Permit Number 03042121
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN.
 2) 909.1 WASH MACHINE & LAUNDRY SINK
 SHALL NOT DRAIN INTO THE HORIZONTAL WET
 VENT OF THE BATHROOM GROUP. W/M & L/T
 SHALL TIE IN DOWNSTREAM OF THE BATHROOM
 GROUP.
 3) VERTICAL RISE ON AN ISOMETRIC INDICAT
 ES A SECOND FLOOR.
 4) 905.3 NO HORIZONTAL DRY VENTS.
 5) KITCHEN SINK MISLABLED AS LAVS.
 6) BIDET NOT VENTED
 7) PIPE SIZES MISSING
 (SEE SHEET ATTACHED TO PERMIT #03041590
 FOR AN EXAMPLE OF APPROVED SANT. RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692