| Plan Review Notes For Permit 03042121 |
| Permit Number |
03042121 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-13 00:00:00 | PROVISO | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE CORRECT THE FOLLOWING FOR CODE | | | COMPLIANCE AND RESUBMIT FOR | | | REVIEW,PRIOR TO ROUGH INSPECTION. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE #2 PER 250-66 & MUST BE | | | CONTINUOUS PER 250-64(C). | | | | | | 2} RECEPTACLES NEED TO BE ADDED IN THE | | | LIBRARY TO COMPLY WITH 210-52(A)(1). | | | | | | 3} THE RECEPTACLE SPACING IN THE LIVING | | | ROOM DOES NOT MEET 210-52 AND ARE SHOWN | | | OFF THE WALL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|