| Date |
Text |
| 2003-06-04 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SOIL BORING TEST REPORT AS |
| | REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| | |
| | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | INDICATE THE ABOVE ON THE PLANS. |
| | |
| | 5) THE SITE PLAN DOES NOT INDICATE THE |
| | DISTANCE TO THE BUILDING LINES TO THE |
| | PROPERTY LINES. THE PLAN WAS SCALED TO |
| | DETERMINE THE DISTANCE FROM THE PROPERTY |
| | LINE TO THE WALL AT THE LEFT ELEVATION. |
| | IT WAS DETERMINED TO BE OVER 20' FOR |
| | TABLE 600 CALCULATIONS. |
| | |
| | 6) REVISE WINDLOAD SCHEDULE ON A1 TO |
| | REFERENCE THE CURRENT CODE WHICH IS THE |
| | 2001 FBC. ALSO THE NEGATIVE PRESSURES |
| | ARE GIVEN WITH POSITIVE SIGNS. |
| | |
| | 7) SOME TEXT ON A2 IS UPSIDE DOWN. |
| | |
| | 8) THE FOUNDATION PLAN DOES NOT INDICATE |
| | THE AMOUNT OF RECESS FOR THE MASTER BATH |
| | SHOWER OR THE SHOWER IN BATH #4. PLEASE |
| | CLARIFY. |
| | |
| | 9) PROVIDE A FULL BATH WITH A DOOR THAT |
| | HAS A 29" CLEAR OPENING. SEE FBC CHAPTER |
| | 11. |
| | |
| | 10) SAFETY GLAZING IS REQUIRED IN THE |
| | MASTER BATH WINDOW PER FBC 2405.2. |
| | |
| | 11) REVISE BUCK DETAILS ON A4. THE S.G.D |
| | AND WINDOW FRAMES ARE REQUIRED TO BE |
| | FASTENED THROUGH THE 1X BUCKS INTO THE |
| | COCRETE SUBSTRATE. THE 2X DOOR BUCKS ARE |
| | REQUIRED TO EXTEND TO THE INTERIOR FACE |
| | OF THE DOOR JAMB. SEE FBC 1707.4.2.2. |
| | |
| | 12) THE 2' WIDE CASEMENT WINDOWS IN |
| | BEDROOM #2 ON A4 DO NOT COMPLY WITH THE |
| | EGRESS REQUIREMENTS OF FBC 1005.4. |
| | |
| | 13) INDICATE ON PLANS THAT LIBRARY IS |
| | NOT TO BE USED AS A SLEEPING ROOM OR |
| | PROVIDE WINDOWS THAT COMPLY WITH FBC |
| | 1005.4. |
| | |
| | 14) THE ADJACENT WALL IN THE GARAGE IS |
| | REQUIRED TO BE INSULATED AND THE DOOR TO |
| | CONDITIONED SPACE IS REQUIRED TO BE |
| | SOLID CORE OR INSULATED. INDICATE THIS |
| | ON A3 OF PLANS. |
| | |
| | 15) UPDATE THE TRUSS ANCHOR SCHEDULE ON |
| | A5. HUGHES WAS PURCHASED BY USP SOMETIME |
| | AGO AND ARE NO LONGER BEING PRODUCED. |
| | NOTE: THE 2001 FBC NO LONGER ALLOWS THE |
| | ONE THIRD INCREASE IN STEEL CALCULATIONS |
| | THEREFORE, THE VALUES FOR SOME TRUSS |
| | CONNECTORS ARE LOWER. SEE THE 2003 USP |
| | CATALOG OR THE 2002 SIMPSON HIGH WIND |
| | CATALOG FOR CORRECTED VALUES. |
| | |
| | 16) THE TIE BEAMS FOR THE GOLF CART |
| | GARAGE DOOR AND THE LIBRARY WINDOWS ARE |
| | NOT INDICATED ON THE ROOF PLAN ON A5. |
| | TB-8 IS INDICATED IN THE MIDDLE OF THE |
| | LIBRARY. |
| | |
| | 17) SPECIFY THE LENGTH/EMBED DEPTH OF |
| | THE #5 STUDS FOR THE EMBED CONNECTOR AND |
| | THE WEDGE ANCHORS AND EXPANSION BOLTS |
| | FOR THE TRUSS ANCHORS AND HOLD DOWNS ON |
| | A5. |
| | |
| | 18) THE ROOF/FLOOR TRUSS ANCHOR NOTES ON |
| | A5 INCORRECTLY STATES THAT THE LOAD |
| | VALUES OF A STRAP INCREASES IN MULTIPLES |
| | OF THE NUMBER OF STRAPS. THE CONE PULL |
| | OUT OF THE CONCRETE BEAM LIMITS THE LOAD |
| | VALUES FOR MULTIPLE STRAPS. SEE TRUSS |
| | CATALOGS FOR LOAD VALUES OF MULTIPLE |
| | STRAPS. |
| | |
| | 19) PROVIDE A ROOF SHEATHING NAILING |
| | SCHEDULE. SEE CITY AMENDMENTS TO 2001 |
| | FBC TABLE 2306.1. |
| | |
| | 20) INDICATE THE CEILING FINISHES FOR |
| | THE ENTRY AND COVERED PATIO. |
| | |
| | 21)UPDATE THE TRUSS CONNECTORS SPECIFIED |
| | ON A6. |
| | |
| | 22)THE SECTIONS ON A6 ARE NOT IDENTIFIED |
| | BY NUMBER AND SOME OF THE TEXT IS |
| | UPSIDE DOWN. |
| | |
| | 23) THE DIMENSIONS AT THE LIVING ROOM |
| | WINDOW ON THE REAR ELEVATION INDICATES |
| | 1' BETWEEN THE WINDOWS. PLEASE CLARIFY. |
| | |
| | 24) THE CONDITIONED FLOOR AREA ON THE |
| | ENERGY CALCULATIONS DOES NOT MATCH THE |
| | A/C AREA LISTED ON A4 OF THE PLANS. |
| | |
| | 25) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - CASEMENT WINDOWS |
| | - NEED SBCCI REPORT 9606C IN ADDITION TO |
| | THE DRAWING FOR THE OVERHEAD GARAGE DOOR |
| | - THE MULLIONS DO NOT MEET THE WINDLOAD |
| | PRESSURES FOR THE OPENING AT THE LIVING |
| | ROOM WINDOW. THE PRODUCT APPROVAL ALSO |
| | LIMITS THE NUMBER OF WINDOWS MULLED |
| | TOGETHER TO 5 UNITS. |
| | |
| | 26) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR THE OPTIONAL |
| | BBQ IF IT IS TO BE INSTALLED. |
| | |
| | 27) REFER TO NOTES WRITTEN ON PLANS. |
| | SUBMIT THE OLD PAGES ALONG WITH NEW, |
| | WHEN RESUBMITTING. |
| | |
| | 28) 1803.1.3 EXCAVATION FOR ANY PURPOSE |
| | SHALL NOT EXTEND WITHIN 1 FT OF THE |
| | ANGLE OF REPOSE OR NARURAL SLOPE OF THE |
| | SOIL UNDER ANY FOOTING OR FOUNDATION, |
| | UNLESS SUCH FOOTING OR FOUNDATION IS |
| | FIRST PROPERLY UNDERPINNED OR PROTECTED |
| | AGAINST SETTLEMENT. PLEASE BE AWARE OF |
| | THIS WHEN EXCAVATING FOR POOL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |