Plan Review Notes
Plan Review Notes For Permit 03042120
Permit Number 03042120
Review Stop E
Sequence Number 2
Notes
Date Text
2003-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR MUST BE INSTALLED
 PER 250.64C,AND BE #2.REMOVE #4.
  
 PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
 A RUBBER STAMP IS NOT ACCEPTABLE AS A
 SIGNATURE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW