| Plan Review Notes For Permit 03042120 |
| Permit Number |
03042120 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-02 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT THE GROUNDING | | | ELECTRODE CONDUCTOR MUST BE INSTALLED | | | PER 250.64C,AND BE #2.REMOVE #4. | | | | | | PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | A RUBBER STAMP IS NOT ACCEPTABLE AS A | | | SIGNATURE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|