Plan Review Notes
Plan Review Notes For Permit 03042120
Permit Number 03042120
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE DRAWINGS.
  
 2} THERE IS NO PANEL SCHEDULE FOR PANEL
 "B".
  
 3} ADD A RECPTACLE IN THE BREAKFAST AREA
 PER 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718