| Plan Review Notes For Permit 03042120 |
| Permit Number |
03042120 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-14 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SHOW THE LOCATION OF THE SERVICE | | | EQUIPMENT ON THE DRAWINGS. | | | | | | 2} THERE IS NO PANEL SCHEDULE FOR PANEL | | | "B". | | | | | | 3} ADD A RECPTACLE IN THE BREAKFAST AREA | | | PER 210-52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|