| Plan Review Notes For Permit 03042119 |
| Permit Number |
03042119 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-11-09 00:00:00 | BUILDING PROVISO: | | | 1-RESUBMIT PRODUCT APPROVAL FOR GARAGE | | | DOOR WITH DRAWINGS THAT ARE LEGIBLE. | | | | | | 2-PROVIDE PRODUCT APPROVAL FOR FIXED | | | WINDOWS FOR LARGE SIZE WINDOW AS SHOWN | | | ON PLANS AT MASTER BEDROOM. | | | | | | 3-PROVIDE UL LISTING AND COMPLETE SPECS | | | PACKAGE FOR FIREPLACE AND BBQ AS REQ'D | | | BY SECTIONS 2806 & 2808 FBC 2001. | | | | | | 4-PROVIDE COMPLETE FRAMING DETAILS AND | | | SPECS FOR COLUMNS BETWEEN FRENCH DOORS | | | AT FAMILY ROOM AREA. SEC. 104.2.1.2 | | | CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 5-PROVIDE COMPLETE SPECIFICATIONS FOR | | | ROOF TILE SYSTEM FASTENING AS REQUIRED | | | BY SEC. 104.2.1.1 CITY AMENDMENTS TO | | | FBC | | | | | | 6-ROOF FRAMING PLAN TO INCLUDE 10PSF OR | | | 30PSF ATTIC LIVE LOAD AS REQ'D BY TABLE | | | 1604.1 FBC 2001. REVISE AS REQUIRED. | | | | | | 7-REVISE TRUSS ANCHOR SCHEDULE. TA22 | | | CONNECTOR DON'T PROVIDE 5" MIN. | | | EMBEDMENT AND REVISE NUMBER OF FASTENERS | | | SPECIFIED FOR TAPL14. SEE USP CATALOGUE | | | AND REVISE AS REQUIRED. |
|