2003-07-14 00:00:00SECOND CHECKLIST:
 1-DRAWINGS TO HAVE ORIGINAL SIGNATURE
 (NO RUBBER STAMP) AS REQ'D BY CHAPTER
 481 FLORIDA STATUTES WHEN SUBMITTING
 DRAWINGS FOR PUBLIC RECORDS
 **ALSO, ARCHITECT NEED TO INCLUDE HIS
 LICENSE #. SEE CHAPTER 481 FL. STATUTE
 2-PAY IMPACT FEES AND BRING BACK PAID
 RECEIPT AND STAMPED DRAWINGS.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-PROVIDE COMPLETE DETAIL AND SPECS FOR
 CONCRETE BOLLARD IN THE GARAGE TO
 PROTECT WATER HEATER. SPECIFY HOW IS
 CONCRETE POST REINFORCED AND SPECIFY
 ANCHORING AT THE BASE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE AT LEAST ONE COMPLETE BATHROOM
 (NO THE POWDER ROOM) WITH DOOR THAT
 ALLOWS 29" CLEAR OPENING AS REQUIRED
 BY SECTION 11-11 FBC 2001.
 6-AHU HANGING DETAIL: A)SPECIFY SIZE OF
 HANGING ROD OR CHAIN.
 B)CLARIFY WHY IS UNIT HANGING FROM BOTT.
 CHORD AND NOT THE TOP CHORD. ALSO,
 NEED TO PROVIDE SPECS TO TRUSS ENG'R
 TO DESIGN BOTTOM CHORD TO RECEIVE THIS
 AHU LOAD. SECTION 104.2.1.2 OF CITY
 AMENDMETS TO FBC 2001.
 7-ENERGY CALCULATIONS WERE NOT REVISED:
 A)DON'T MATCH ORIENTATION OF THIS HOUSE.
 IT WAS DONE FOR LOT #6. NEED WORST
 CASE SCENARIO CALCS. OTHERWISE, NEED
 SITE SPECIFIC ENERGY CALCULATIONS.
 B)NEED PREPARER'S ORIGINAL SIGNATURE.
 C)PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, INCLUDING OWNER.
  
 8-CHIMNEY FRAMING PLAN AND SECTION DON'T
 MATCH. CLARIFY ANCHORS TO BE USED AND
 ATTACHMENT TO TOP CHORD OR BOTTOM
 CHORD OF THE TRUSSES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 ALSO, DETAIL IS INCOMPLETE. SEE PLANS
 9-PROVIDE COMPLETE STRUCTURAL DETAIL
 FOR ATTACHMENT OF 2X BUCKS TO STEEL
 COLUMN. SPECIFY ALL FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-CLARIFY DETAIL FOR TOP OF COLUMN CAP.
 THERE ARE 2 DIFFERENT SIZES OF NELSON
 STUDS SPECIFIED ON THE DETAIL.
 11-REVISE SPACING SPECIFIED FOR WWM
 SUPPORTS FOR CONCRETE SLAB. SEE SEC.
 1909.3 FBC 2001.
 12-OWES $442.89 FOR UPDATED VALUATION
 AND RADON FEES. ALSO, THERE WILL BE
 ADDITIONAL RE-SUBMITTAL FEES.
 13-NEED PRODUCT APPROVAL FOR: A)GARAGE
 SIDE DOOR. B)GARAGE DOORS. C)ENTRY
 DOORS WITH TRANSOM ABOVE ASSEMBLY AS
 SHOWN ON PLANS. D)FIXED WINDOWS WITH
 SIZES AS SHOWN ON PLANS. E)WINDOWS AND
 DOORS MULLIONS. F)FRENCH DOORS WITH
 TRANSOM ABOVE AS SHOWN ON PLANS.
 G)FIREPLACE UL LISTING AND COMPLETE
 SPECS. H)BBQ UL LISTING AND SPECS.
 I)ROOF TILE. J)OVAL AND ARCHED WINDOWS
 AS SHOWN ON PLANS.
 **NOTE: PROVIDE IMPACT RESISTANT GLASS
 AND MULLIONS PRODUCT APPROVALS AS
 SPECIFIED ON PLANS. OTHERWISE, PROVIDE
 COMPLETE STORM SHUTTERS INFORMATION.
  
 14-SHEET A2: A)UPDATE SEMCO CONNECTOR
 SPECIFY ON SECTION DETAIL. SEE PLAN.
 B)WHERE IS WOOD LEDGER DETAIL #3. SEE
 PLANS FOR COMMENTS.
 15-SHEET A3: A)SPECIFY COLUMNS BY LIVING
 ROOM. SEE PLANS FOR COMMENTS.
 B)CLARIFY STEEL COLUMN DETAILS. THERE
 ARE DIFFERENT ANCHOR SIZES SPECIFIED.
 REVISE AS REQUIRED.
 16-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEC. 2405.2 FBC 2001. SEE PLANS.
 17-SHEET A5: MISSING SOME CONNECTORS.
 SEE PLANS FOR COMMENTS.
 18-PROVIDE SOIL TEST REPORT.
 19-PROVIDE COMPLETE SPECS FOR CEILING
 CONSTRUCTION AT FRONT AND REAR PORCH.
 SEE ASTM C926 AND ASTM C1063 FOR MIN.
 STUCCO THICKNESS AND MIN. FASTENER
 TYPE AND SPACING.
 20-UPDATE TRUSS ANCHOR SCHEDULE. SEE
 USP 2003 CATALOGUE & SEC. 1609.4.3
  
 FBC 2001.