| Notes |
| Date |
Text |
| 2003-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. WASH MACHINE SHALL | | | TIE IN DOWNSTREAM OF LAUNDRY SINK, (NOT | | | ON L/SINK WASTE ARM), AND REQUIRES A | | | TRAP AND A STANDPIPE. - LABLE LAUNDRY | | | SINK, (NOT LAV), - CLEAN OUT SHALL BE | | | LOCATED 4' ABOVE FINISHED FLOOR ABOVE | | | WASH MACHINE. - BIDET MISSING FROM RISER | | | - SHOWER FOR CABANA MISSING FROM RISER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|