Plan Review Notes
Plan Review Notes For Permit 03042119
Permit Number 03042119
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-13 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #2 PER 250-66 AND CONTINUOUS
 PER 250-64(C).
  
 2} THE SMOKE DETECTORS AT THE MASTER BED
 ROOM MUST BE INSIDE THE ROOMS TO COMPLY
 WITH 8-1.4.2 NFPA-72.
 A) BEDROOM #4 AS WELL.
  
 3} ADD RECEPTACLES IN THE LIBRARY TO
 COMPLY WITH 210-52(A)(1).
  
 4} ADD A RECEPTACLE IN THE LIVING ROOM
 TO COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718