| Plan Review Notes For Permit 03042119 |
| Permit Number |
03042119 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-13 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO ROUGH INSPECTION. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE #2 PER 250-66 AND CONTINUOUS | | | PER 250-64(C). | | | | | | 2} THE SMOKE DETECTORS AT THE MASTER BED | | | ROOM MUST BE INSIDE THE ROOMS TO COMPLY | | | WITH 8-1.4.2 NFPA-72. | | | A) BEDROOM #4 AS WELL. | | | | | | 3} ADD RECEPTACLES IN THE LIBRARY TO | | | COMPLY WITH 210-52(A)(1). | | | | | | 4} ADD A RECEPTACLE IN THE LIVING ROOM | | | TO COMPLY WITH 210-52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|