Plan Review Notes
Plan Review Notes For Permit 03042119
Permit Number 03042119
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-10 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-UPDATE WIND LOAD CRITERIA ON SHEET A1.
 SEE FBC 2001, NOT SBC 1997. **REVISE
 THE DESIGN PRESSURES AND PROVIDE ALL
 5 ITEMS REQUIRED BY SEC. 1606.1.7 FBC.
 4-PROVIDE COMPLETE DETAIL AND SPECS FOR
 PROTECTION OF GAS WATER HEATER IN THE
 GARAGE. SEC. 104.2.1.2 CITY AMENDMENTS
 5-PROVIDE AT LEAST ONE COMPLETE BATHROOM
 WITH DOOR THAT PROVIDES 29" CLEAR OP'G
 AS REQUIRED BY SEC. 11-11 FBC 2001.
 6-PROVIDE COMPLETE STRUCTURAL DETAIL AND
 SPECIFICATIONS FOR HANGING AIR HANDLER
 UNIT FROM CEILING. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-ENERGY CALCULATIONS: A)THIS ENERGY
 CALCULATIONS DON'T MATCH ORIENTATION
 OF THIS HOUSE. THIS IS NOT A WORST
 CASE CALCULATION. THEREFORE, ENERGY
 CALCS SHALL BE DONE TO THE SPECIFIC
 ORIENTATION OF THE HOUSE. REVISE AS
 REQUIRED. AND, NEED ORIGINAL SIGNATURE
 B)NEED ORIGINAL SIGNATURE BY PREPARER OF
 THE ENERGY CALCULATIONS.
 C)PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM. EG: OWNER, ETC.
 8-PROVIDE COMPLETE FRAMING INFORMATION
 FOR CUPOLAS & CHIMNEY. PROVIDE FRAMING
 PLANS & STRUCTURAL WALL SECTIONS THAT
 SHOW ALL FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE COMPLETE STRUCTURAL FRAMING
 DETAILS AND SPECS FOR CONNECTIONS OF
 WINDOWS AND STRUCTURAL MULLIONS TO THE
 STEEL COLUMNS AT LIVING ROOM AREA.
 SEE PRODUCT APPROVALS FOR REQUIRED
 INFORMATION. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-PROVIDE DETAIL/SPECS FOR CONNECTION
 AT TOP OF STEEL COLUMNS AT LIVING AREA
 WINDOWS AND AT ENTRY PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-PROVIDE SPECS FOR WWM SUPPORTS AS
 REQUIRED BY SEC. 1909.3 FBC 2001.
 12-REVISE STRUCTURAL BUCK DETAIL FOR
 DOORS USING 2X BUCK. SEE SECTION
 1707.4.4.2 FBC 2001.
 13-OWES $442.89 FOR UPDATED VALUATION
 AND RADON FEES.
 14-PROVIDE PRODUCT APPROVAL FOR:
 A)GARAGE SIDE DOOR.
 B)GARAGE DOORS.
 C)ENTRY DOORS W/ TRANSOM ABOVE ASSEMBLY
 AS SHOWN ON PLANS.
 D)FIXED WINDOWS. SIZES AS SHOWN ON PLANS
 E)FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY
 AS SHOWN ON PLANS.
 F)WINDOW & DOOR MULLION AS SHOWN ON PLAN
 G)FIREPLACE LISTING AND COMPLETE SPECS.
 H)BBQ UL LISTING AND COMPLETE SPECS.
 I)ROOF TILE.
 J)OVAL & ARCHED WINDOWS AS SHOWN ON PLAN
  
 15-SHEET A2: A)UPDATE SEMCO CONNECTOR
 SPECIFIED ON SECTION. ALSO, WHERE IS
 WOOD LEDGER DETAIL 3?. SEE PLAN.
 B)TYP. WALL SECTION: UPDATE HUGHES
 CONNECTOR SPECIFIED (NOT IN BUSINESS).
  
 16-SHEET A3: A)SPECIFY COLUMN BY FAMILY
 ROOM AREA. SEE PLAN.
 B)THERE ARE DIFFERENT SPECS FOR STEEL
 COLUMNS. CLARIFY. SEE COMMENTS ON PLAN
  
 17-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE SHEET A4 AND SEC. 2405.2 FBC 2001.
 18-SHEET A5: MISSING SOME CONNECTORS AND
 SEE PLAN FOR ADDITIONAL COMMENTS.
 19-PROVIDE SOIL TEST REPORT.
 20-PROVIDE SPECIFICATIONS FOR CEILING
 CONSTRUCTION AT REAR AND FRONT PORCH.
 SPECIFY ALL FASTENERS. SEE ASTM C-926
 AND ASTM C-1063.
 **ALSO, SPECIFY STUCCO THICKNESS OF 7/8"
 AT FRAMED WALLS AS REQ'D BY ASTM C-926
 21-UPDATE TRUSS ANCHOR SCHEDULE TO
 COMPLY WITH SECTION 1606.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE ALLOWABLE
 STRESS INCREASE TO BE USED. SEE USP
 CATALOGUE THAT HAS UPDATED VALUES.
 22-PROVIDE ROOF SHEATHING NAILING
 DIAPHRAGM SHOWING FASTENERS & SPACING
 AND SHOWING NAILING ZONES. SEE SECTION
 2306 CITY AMENDMENTS TO FBC 2001.
 23-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS. INCLUDING KEY PLAN,
 INSTALLATIONSCHEDULE, AND CLEARLY
 MARK ON ENGINEERED DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN, DESIGN PRESSURES & STRUCTURE TO
 BE ATTACHED TO.