| Notes |
| Date |
Text |
| 2003-05-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT P0.1 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL IS REQUIRED. PLEASE | | | PROVIDE ON DETAIL. SECTION 607.3.2 | | | 2) SHT P5.1 WATER RISER DIAGRAM. WATER | | | HAMMER ARRESTORS REQUIRED BY SECTION | | | 604.9 SHALL BE LOCATED NEAR THE FIXTURE, | | | IN AN "EFFECTIVE RANGE" NOT AT THE TOP | | | OF THE DROP IN THE CEILING. PDI-WH 201 | | | AND MANUF. INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|