| 2003-07-01 00:00:00 | ********CORRECTIONS******** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE THE PREVIOUS CORRECTIONS |
| | REGARDING THE ATTACHMENT OF THE NEW SLAB |
| | TO THE EXISTING.THE EMBEDMENT LENGTH |
| | IS STILL NOT ON THE PLAN.AGAIN, I |
| | HAVE CIRCLED THE DETAIL SO THAT YOU |
| | CORRECT THE RIGHT ONE. |
| | |
| | 2.)SEE THE CORRECTION NOTE #5 DATED |
| | 6/12/3.I HAD A CONVERSATION WITH THE |
| | DESIGNER EXPLAINING THIS CORRECTION.HE |
| | INDICATED THAT HE UNDERSTOOD THE |
| | CORRECTION.IT IS NOT CHANGED ON THE |
| | PLAN.THE R VALUE SPECIFIED ON THE |
| | PLAN IN NOT CONSISTENT WITH THE |
| | MINIMUMS SPECIFIED ON THE ENERGY CALC. |
| | I HAVE CIRCLED THE INCORRECT RVALUE ON |
| | THE PLAN. |
| | |
| | 3.)THE PRODUCT APPROVALS FOR THE |
| | HURRICANE SHUTTERS ARE ILLEGIBLE. |
| | |
| | 4.)PROVIDE A HURRICANE SHUTTER |
| | ANCHORING SCHEDULE, SEE ATTACHED. |
| | |
| | 5.)SHOW THE DIMENSIONS ABOVE & BELOW |
| | GRADE FOR THE FOOTER, CBS WALL SECTION. |
| | |
| | 6.)THE WINDOW PRODUCT APPROVALS ARE |
| | INCOMPLETE.SUBMIT TWO COMPLETE COPIES. |
| | |
| | 7.)ADDITIONS OVER 25% MUST COMPLY |
| | WITH FBC3401.7.1.2.SHOW, FOR THE |
| | EXISTING HOUSE, THE FOLLOWING: |
| | EMERGENCY EGRESS FOR BEDROOMS,FBC1005.4 |
| | SMOKE DETECTORS FOR BEDROOMS,FBC905.2.2 |
| | BATHROOM TO COMPLY WITH FBC11-11(1) |
| | FRONT DOOR TO COMPLY WITH 1004 |
| | |
| | 8.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |