| 2003-06-12 00:00:00 | *******CORRECTIONS******** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE #2 ON FIRST CORRECTION LIST, |
| | #1 ON 2ND CORRECTION LIST.THIS IS |
| | THE THIRD REQUEST FOR ENERGY CALCS.A |
| | PERMIT CANNOT BE ISSUED UNTIL ENERGY |
| | CALCS ARE SUBMITTED. |
| | |
| | 2.)SEPARATE PERMITS REQUIRED. |
| | |
| | 3.)SEE PREVIOUS CORRECTION #3, |
| | FOR THE ATTACHMENTS OF THE NEW SLAB TO |
| | THE EXISTING, SHOW THE LENGTH OF THE |
| | DOWELS AND THE EMBEDMENT.THIS IS |
| | FOUND ON THE WALL SECTION; I HAVE |
| | CIRCLED IT SO THAT YOU CHANGE THE |
| | CORRECT DETAIL. |
| | |
| | 4.)SEE PREVIOUS CORRECTION #5; STILL |
| | SHOWS BOTH A 6" AND 8" EMBEDMENT.I |
| | HAVE MARKED THIS AS WELL. |
| | |
| | 5.)YOU HAVE SPECIFIED 4.2 FOIL |
| | INSULATION ON THE WALL.THIS MUST BE |
| | CONSISTENT WITH THE ENERGY CALCS.IF |
| | THEY SUBMIT A SHORT FOR ENERGY CALC, |
| | THE MINIMUM R VALUE FOR A BLOCK WALL |
| | IS R5.DO NOT RESUBMIT UNTIL YOU HAVE |
| | SEEN THE ENERGY CALC AND HAVE CONFIRMED |
| | THAT THE R VALUES STATED ON THE ENERGY |
| | CALC ARE CONSISTENT WITH OR LESS THAN |
| | SPECIFIED BY YOUR PLAN. |