| 2003-05-20 00:00:00 | *******CORRECTIONS******* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)IMPACT FEES ARE TO BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025. |
| | |
| | 2.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 3.)SEPARATE PERMITS REQUIRED (ELECTRIC |
| | ROOF, MECHANICAL). |
| | |
| | 4.)IS THE 18 X 16 FOOTER ON THE PLAN |
| | PROPOSED OR EXISTING?IF IT IS A NEW |
| | FOOTER, HOW WILL IT TIE INTO THE |
| | EXISTING SLAB? |
| | |
| | 5.)SPECIFY INSULATION ON THE PLAN (NOT |
| | "SEE ENERGY CALC"; ENERGY CALCS NOT |
| | SUBMITTED). |
| | |
| | 6.)SOFFIT VENTS MUST COMPLY WITH FBC |
| | 2309.7; CANNOT "MATCH EXISTING". SPECIFY |
| | SIZE AND SPACING. |
| | |
| | 7.)ROOF SHEATHING ATTACHMENT DOES NOT |
| | COMPLY WITH CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC, REVISED TABLE |
| | 2306.1 FOR ZONE 3. |
| | |
| | 8.)SECTION A A-1 IS LABELED "MAIN |
| | FLOOR STAIR".REVISE. |
| | |
| | 9.)PROVIDE WINDOW & DOOR BUCK |
| | ATTACHMENT DETAILS; REFER TO FBC |
| | 1707.4.4.2. |
| | |
| | 10.) THE ROOF FRAMING PLAN SPECIFIES |
| | 2X8S, THE WALL SECTION SPECIFIES 2X10S. |
| | |
| | 11.) TYPICAL INTERIOR PARTITION DETAIL |
| | REFERS TO AN ANCHOR SCHEDULE NOT ON THE |
| | PLAN.ALSO IT IS UNCLEAR AS TO WHERE |
| | THIS PARTITION IS TO BE INSTALLED. |
| | |
| | 12.)THE BEAM TO ROOF JOIST CONNECTION |
| | IS INCORRECT.SPECIFY THE CORRECT |
| | ATTACHMENT WITH CORRECT LANGUAGE AS TO |
| | HOW IT WILL BE ATTACHED (SIZE AND |
| | NUMBER).REFER TO THE 2003 CATALOG. |
| | |
| | 13.)WALL SECTION REFERS TO A3; NOT |
| | ON PLAN. |
| | |
| | 14.)ON THE ROOF FRAMING PLAN AND |
| | FOUNDATION PLAN THERE IS A #5 DOWEL TO |
| | ATTACH TO EXISTING; HOW LONG? |
| | |
| | 15.)THE WIND INFORMATION REFERS TO |
| | TRUSS LOADS; THIS JOB IS USING ROOF |
| | JOISTS. |
| | |
| | 16.)CONFIRM THAT TRACO (SINGLE HUNG |
| | WINDOW PRODUCT APPROVAL SUBMITTED) MAKES |
| | A 345 SINGLE HUNG WINDOW WITH A CLEAR |
| | NET OPENING FOR EMERGENCY EGRESS. |
| | |
| | 17.)IMPACT PROTECTION FOR WINDOWS |
| | REQUIRED; FBC 1606.1.4. |
| | |
| | 18.)PROVIDE PRODUCT APPROVALS FOR THE |
| | IMPACT PROTECTION AND ROOF. |
| | |
| | 19.)ADDITIONAL FEES REQUIRED. |