Plan Review Notes
Plan Review Notes For Permit 03042067
Permit Number 03042067
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-14 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES ON
 THE PLAN FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} THE #4 GEC IS NOT CORRECT FOR A 400
 AMP SERVICE. 1/0 PER 250-66.
  
 2} THERE IS NO PANEL SCHEDULE FOR PANEL
 "B".
  
 3} SHOW THE LOCATION FOR PANEL "B".
  
 4} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED AT 1500 VA PER 220-16(B).
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718