| Plan Review Notes For Permit 03042066 |
| Permit Number |
03042066 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-12 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | TO THE PLANS FOR CODE COMPLIANCE AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} THE #4 GEC IS INCORRECT FOR A 400 AMP | | | SERVICE.#1/0 PER 250-66. | | | | | | 2} THERE IS NO PANEL SCHEDULE FOR SUB | | | PANEL "B". | | | | | | 3} SHOW THE LOCATION OF SUB PANEL "B" ON | | | THE PLANS. | | | | | | 4} THE LAUNDRY CIRCUIT MUST BE | | | CALCULATED AT 1500 VA PER 220-16(B) | | | | | | 5} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|