Plan Review Notes
Plan Review Notes For Permit 03042066
Permit Number 03042066
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-12 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} THE #4 GEC IS INCORRECT FOR A 400 AMP
 SERVICE.#1/0 PER 250-66.
  
 2} THERE IS NO PANEL SCHEDULE FOR SUB
 PANEL "B".
  
 3} SHOW THE LOCATION OF SUB PANEL "B" ON
 THE PLANS.
  
 4} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED AT 1500 VA PER 220-16(B)
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718