| Plan Review Notes For Permit 03042048 |
| Permit Number |
03042048 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-07 00:00:00 | DENIED: | | | PLANS FOR THE OFFICE AREA ARE APPROVED. | | | PLEASE PROVIDE ADDITIONAL INFORMATION | | | AS REQUESTED BY HAROLD PISKURA ON HIS | | | REVIEW DATED 5/29/03. | | | | | | 1.INDICATE HOW FREON & OXEACETALINE | | | GAS ARE TO BE STORED. | | | | | | 2.PROVIDE SEPARATION BETWEEN GAS & | | | FREON. | | | | | | 3.PROVIDE HOW MANY POUNDS OF EACH | | | ITEM TO BE STORED.INDICATING THE | | | NUMBER OF CYLINDERS DOES NOT GIVE AN | | | ACCURATE AMOUNT IN POUNDS. | | | | | | 4.INDICATE ANY LEAK DETECTORS THAT | | | MAY BE REQURIED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|