Plan Review Notes
Plan Review Notes For Permit 03041995
Permit Number 03041995
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-30 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND RECEIPT.
 2-LEFT ELEVATION SHOWS THE PRIVACY WALL,
 BUT IT NOT SHOWN ON FOUNDATION PLAN.
 3-GLASS BLOCK AT BATHROOM AREAS TO BE
 SAFETY GLASS IF FACE THICKNESS IS LESS
 THAN 0.25". SEC. 2405.2 FBC 2001.
 4-PROVIDE COMPLETE DETAILS AND FASTENER
 SPECIFICATIONS FOR INSTALLATION OF
 HANGING AIR HANDLING UNIT.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE DETAIL FOR GARAGE STRUCTURAL
 BUCK DETAIL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 6-UPDATE TRUSS ANCHOR SCHEDULE, DETAIL
 3/A14, 2/A14 AND ALL DETAILS THAT NEED
 TO REVISE THE LOADS TO COMPLY W/ SEC.
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW 33% ALLOWABLE STRESS INCREASE
 TO BE USED. SEE USP 2003 CATALOGUE FOR
 REVISED LOADS.
 7-REVISE DETAIL 4/14. NEED 2X BUCK TO
 SUPPORT WINDOW. SEE PRODUCT APPROVAL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-ENERGY CALCULATIONS: PROVIDE COMPLETE
 INFORMATION ON TOP OF FORM INCLUDING
 CORRECT OWNER.
 9-NEED TO UPDATE WORKERS COMPENSATION.
 10-DESIGN CRITERIA SPECIFIED ON SHEET
 C-1 CALLS FOR EXPOSURE "D", BUT DESIGN
 PRESSURES SHOWN ON ELEVATIONS DON,T
 MATCH. REVISE AS REQUIRED.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-PROVIDE ATTIC ACCESS AT FAMILY ROOM
 WING, MASTER BATH AREA AND AT MASTER
 BEDROOM AREA. (ONE SHON ON MASTER BED-
 ROOM CLOSET DOESN'T WORK BECAUSE THE
 2ND FLOOR IS ABOVE THIS CLOSET). SEC.
 2309.6 FBC 2001.
 12-SPECIFY SAFETY GLASS AT LIVING ROOM
 AREA. SECTION 2405.2 FBC 2001.
 13-SHEET A-3: REVISE HANDRAIL HEIGHT.SEE
 SEC. 1007.5.1 FBC 2001. **HANDRAIL AND
 GUARDRAIL ARE NOT THE SAME.
 14-PROVIDE COMPLETE 2 STORY WALL SECTION
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 15-PROVIDE SPECS FOR FIREBLOCKING AT ALL
 CONCEALED SPACES. INCLUDING AT STAIRS.
 SEE SEC. 2305 FBC 2001.
 16-STUCCO ON FRAMED WALL TO BE 7/8" MIN.
 SEE ASTM C-926.
 17-WHERE ARE DETAILS 13/A14 AND 14/A14
 SHOWN ON FRAMING PLANS.
 18-REVISE MEAN ROOF HEIGHT. MEAN ROOF HT
 IS TAKEN FROM GRADE, NOT FROM FINISH
 FLOOR. SEC. 104.2.1.2 CITY AMENDMENTS.
 19-REVISE DIAPHRAGM SCHEDULE. NEED 8D
 RING SHANK NAILS WHEN MEAN ROOF HEIGHT
 IS HIGHER THAN 25'. SEE SEC. 2306 OF
 CITY AMENDMENTS TO FBC 2001.
 20-PROVIDE COMPLETE DETAIL/SPECS FOR
 BOLLARD FOR PROTECTION OF EQUIPMENT IN
 GARAGE. SEC. 104.2.1.2 CITY AMENDMENTS
 21-FLAT ROOF ABOVE GARAGE. SPECIFY HOW
 IS WATER RUNNING OFF. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-PROVIDE COMPLETE FRAMING DETAILS FOR
 CURVED STAIRS. SEE SEC. 1007.8.3 FBC
 FOR REQUIRED MIN. DIMENSIONS.
 23-PROVIDE COMPLETE FRAMING PLAN & SPECS
 AT SECOND FLOOR AREA BY THE STAIRS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 24-HOW ARE THE 2X STUDS ON DETAIL 8/A14
 CONNECTED AT THE BASE?. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 25-PROVIDE PRODUCT APPROVAL FOR: A)FLAT
 ROOF SYSTEM. B)WINDOW AT LIVING ROOM
 AREA. C)HORIZONTAL SLIDER WINDOW.
 D)ENTRY DOOR WITH SIDELITE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 E)SITE SPECIFIC ENGINEERING FOR WINDOW
 AT BREAKFAST AREA: DESIGN PRESSURES
 DON'T MATCH THOSE SHOWN ON PLANS.
 ARCHITECT TO SIGN & SEAL SITE SPECIFIC
 FORM AS REQ'D BY THE BLDG OFFICIAL.
 FORM NEEDS TO HAVE THE SITE SPECIFIC
 ADDRESS.
 PROVIDE THE PRODUCT APPROVAL FOR THE
 4500 SERIES WINDOWS.
 FORM AND DRAWINGS DON'T MATCH. EG: SEE
 GLASS THICKNESS.
 26-SEE REVIEWED SET FOR ADDITIONAL
 COMMENTS AND PLEASE RETURN REVIEWED
 SET TO EXPEDITE REVIEW PROCESS.