| Plan Review Notes For Permit 03041993 |
| Permit Number |
03041993 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-EGRESS WINDOW AT GUEST SUITE TO HAVE | | | 20" MINIMUM CLEAR WIDTH OPENING AND | | | 5.0 S.F. MINIMUM TOTAL CLEAR OPENING | | | AS REQUIRED BY SEC. 1005.4 FBC 2001. | | | 2-PROVIDE PRODUCT APPROVAL FOR CASEMENT | | | WINDOWS. | | | 3-AS REQUIRED BY THE BUILDING OFFICIAL, | | | NEED AMMENDED DECLARATION OF COVENANTS | | | RESTRICTIONS AND EASEMENTS SPECIFYING | | | EGRESS EASEMENT WHEN HAVING BEDROOMS | | | ON THE ZERO LOT LINE SIDE. | | | 4-REVISE ENERGY CALCULATIONS. A/C AREA | | | DOESN'T MATCH A/C AREA SHOWN ON | | | ARCHITECT'S PLANS. RE-SUBMIT. | | | 5-AS REQUIRED BY THE BUILDING OFFICIAL, | | | PROVIDE ORIGINAL ENGINEERED DRAWINGS | | | FOR STORM PANELS, SINCE THE ENGINEER | | | IS LIMITING HIS DRAWINGS TO BE USED | | | FOR ONE PERMIT ONLY. SEE STAMP ON | | | ENGINEERED DRAWINGS. |
|