Plan Review Notes
Plan Review Notes For Permit 03041993
Permit Number 03041993
Review Stop B
Sequence Number 2
Notes
Date Text
2003-06-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-EGRESS WINDOW AT GUEST SUITE TO HAVE
 20" MINIMUM CLEAR WIDTH OPENING AND
 5.0 S.F. MINIMUM TOTAL CLEAR OPENING
 AS REQUIRED BY SEC. 1005.4 FBC 2001.
 2-PROVIDE PRODUCT APPROVAL FOR CASEMENT
 WINDOWS.
 3-AS REQUIRED BY THE BUILDING OFFICIAL,
 NEED AMMENDED DECLARATION OF COVENANTS
 RESTRICTIONS AND EASEMENTS SPECIFYING
 EGRESS EASEMENT WHEN HAVING BEDROOMS
 ON THE ZERO LOT LINE SIDE.
 4-REVISE ENERGY CALCULATIONS. A/C AREA
 DOESN'T MATCH A/C AREA SHOWN ON
 ARCHITECT'S PLANS. RE-SUBMIT.
 5-AS REQUIRED BY THE BUILDING OFFICIAL,
 PROVIDE ORIGINAL ENGINEERED DRAWINGS
 FOR STORM PANELS, SINCE THE ENGINEER
 IS LIMITING HIS DRAWINGS TO BE USED
 FOR ONE PERMIT ONLY. SEE STAMP ON
 ENGINEERED DRAWINGS.