| Plan Review Notes For Permit 03041728 |
| Permit Number |
03041728 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | 1) FBC-2001424.2.7.1 POOL CIRCULATING | | | PUMPS SHALL BE EQUIPPED ON THE INLET | | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | | STRAINER WHEN USED WITH A PRESSURE FIL- | | | TER. (DETAIL) | | | 2) FBC-2001 424.2.7.2 PUMPS AND EQUIP- | | | MENT SHALL BE MOUNTED ON A SUBSTANTIAL | | | BASE IN A MANNER THAT WILL ELIMINATE | | | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- | | | AL 4" THICK. (DETAIL) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|