| 2003-07-11 00:00:00 | THE SOUTHERN STRUCTURES LETTER DATED |
| | 6/19/03 AND SIGNED AND SEALED BY NEAL |
| | ROBERTSON CITES A WINDLOAD IMPORTANCE |
| | FACTOR OF 0.77 WHICH IS NOT APPLICABLE |
| | TO THIS BUILDING.THIS WILL BE A |
| | CATEGORY II BUILDING AS DESCRIBED IN |
| | ASCE 7-98 TABLE 1-1 THUS PROVIDING AN |
| | IMPORTANCE FACTOR "I" OF 1.00. |
| | |
| | THE LETTERS REFERENCE TO WOOD STRUCTURAL |
| | PANELS FOR IMPACT RESISTANCE IS INVALID |
| | SINCE THAT SAME CODE SECTION LIMITS |
| | THAT METHOD TO 130 MPH AREAS. |
| | |
| | THE COVER SHEET FOR THE SOUTHERN |
| | STRUCTURES PLAN DATED 6/19/03 HAS THE |
| | STATEMENT UNDER THE HEADING BASIC |
| | DESIGNLOADING "SEE BUILDING CODE TO |
| | OBTAIN |
| | REQUIRED WIND COEFFICIENTS MULTIPLIERS." |
| | |
| | THIS IS NOT AN ACCEPTABLE SUBSTITUTE FOR |
| | SPECIFIC DESIGN CRITERIA.PLEASE |
| | PROVIDE COMPLETE STRUCTURAL |
| | CALCULATIONS, INCLUDING AN |
| | INVESTIGATION OF THE COMPONENTS AND |
| | CLADDING FOR THE ROOF AND WALLS.SEE |
| | FBC 1609 FOR LOAD COMBINATIONS AND |
| | REDUCTIONS PERMITTED FOR ASD. |
| | |
| | PLEASE PROVIDE FLAME SPREAD |
| | DATA/LISTINGS FOR THE EXPOSED VINYL |
| | FACED INSULATION.SEE FBC 708.3. |
| | |
| | SEE THE PROEVIOUS COMMENT LISTS RE: |
| | IMPACT FEES. |
| | |
| | THE DECLARED VALUATION OF $275,000.00 IS |
| | TOO LOW FOR THIS SCOPE OF WORK.THE |
| | CITY ESTIMATE IS $1,727,104.00. |
| | THE REMAINING FEE TOTAL AT THIS TIME IS |
| | $17,601.6O. |