Plan Review Notes
Plan Review Notes For Permit 03041708
Permit Number 03041708
Review Stop B
Sequence Number 2
Notes
Date Text
2003-07-11 00:00:00THE SOUTHERN STRUCTURES LETTER DATED
 6/19/03 AND SIGNED AND SEALED BY NEAL
 ROBERTSON CITES A WINDLOAD IMPORTANCE
 FACTOR OF 0.77 WHICH IS NOT APPLICABLE
 TO THIS BUILDING.THIS WILL BE A
 CATEGORY II BUILDING AS DESCRIBED IN
 ASCE 7-98 TABLE 1-1 THUS PROVIDING AN
 IMPORTANCE FACTOR "I" OF 1.00.
  
 THE LETTERS REFERENCE TO WOOD STRUCTURAL
 PANELS FOR IMPACT RESISTANCE IS INVALID
 SINCE THAT SAME CODE SECTION LIMITS
 THAT METHOD TO 130 MPH AREAS.
  
 THE COVER SHEET FOR THE SOUTHERN
 STRUCTURES PLAN DATED 6/19/03 HAS THE
 STATEMENT UNDER THE HEADING BASIC
 DESIGNLOADING "SEE BUILDING CODE TO
 OBTAIN
 REQUIRED WIND COEFFICIENTS MULTIPLIERS."
  
 THIS IS NOT AN ACCEPTABLE SUBSTITUTE FOR
 SPECIFIC DESIGN CRITERIA.PLEASE
 PROVIDE COMPLETE STRUCTURAL
 CALCULATIONS, INCLUDING AN
 INVESTIGATION OF THE COMPONENTS AND
 CLADDING FOR THE ROOF AND WALLS.SEE
 FBC 1609 FOR LOAD COMBINATIONS AND
 REDUCTIONS PERMITTED FOR ASD.
  
 PLEASE PROVIDE FLAME SPREAD
 DATA/LISTINGS FOR THE EXPOSED VINYL
 FACED INSULATION.SEE FBC 708.3.
  
 SEE THE PROEVIOUS COMMENT LISTS RE:
 IMPACT FEES.
  
 THE DECLARED VALUATION OF $275,000.00 IS
 TOO LOW FOR THIS SCOPE OF WORK.THE
 CITY ESTIMATE IS $1,727,104.00.
 THE REMAINING FEE TOTAL AT THIS TIME IS
 $17,601.6O.