| Plan Review Notes For Permit 03041708 |
| Permit Number |
03041708 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLEASE INDICATE THE NATURE OF MATL'S | | | BEING STORED IN WAREHOUSE. MSDS AND MAN- | | | UFACTURE SHEETS SHALL BE REQUIRED TO DE- | | | TERMINE IF AN EMERGENCY EYEWASH/SHOWER | | | WILL BE REQUIRED PER SECTION 411.1. | | | 2) WATER RISER DIAGRAM REQUIRED. | | | 3) SHUT OFF VALVE REQUIRED FOR HOSE BIBB | | | SECTION 606.2(2). | | | 4) RPZ BACKFLOW REQUIRED ON WATER SERV- | | | ICE. | | | 5) SHT P-1 PLUMBING PROJECT NOTES: | | | #29 AIR CHAMBERS ARE NOT APPROVED. | | | PLEASE DELETE REFERENCE. | | | #34 DIELECTRIC UNIONS ARE ONLY APPROVED | | | FOR GAS APPLICATION. DELETE REFERENCE OR | | | MODIFY NOTE TO READ DIELECTRIC COUPLING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|