2003-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE INDICATE THE NATURE OF MATL'S
 BEING STORED IN WAREHOUSE. MSDS AND MAN-
 UFACTURE SHEETS SHALL BE REQUIRED TO DE-
 TERMINE IF AN EMERGENCY EYEWASH/SHOWER
 WILL BE REQUIRED PER SECTION 411.1.
 2) WATER RISER DIAGRAM REQUIRED.
 3) SHUT OFF VALVE REQUIRED FOR HOSE BIBB
 SECTION 606.2(2).
 4) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 5) SHT P-1 PLUMBING PROJECT NOTES:
 #29 AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE REFERENCE.
 #34 DIELECTRIC UNIONS ARE ONLY APPROVED
 FOR GAS APPLICATION. DELETE REFERENCE OR
 MODIFY NOTE TO READ DIELECTRIC COUPLING.
  