2003-05-19 00:00:00DENIED:
  
 1.DUCT SMOKE DETECTORS SHALL BE R
 INSTALLED IN THE SUPPLY AIR DUCT SYSTEMS
 WITH THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.2001 FBC(M) 606.2.1
  
 2.FAN SHUTDOWN BE DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM STROBE
 IN NORMALLY OCCUPIED AREAS OR ACTIVATE
 A VISIBLE & AUDIBLE SUPERVISORY SIGNAL
 AT A CONSTANTLY ATTENDED LOCATION.
  
 3.CONDENSATE SHALL TERMINATE A
 MINIMUM OF 12" AWAY FROM THE BUILDING
 STRUCTURE.2001 FBC 1503.4.4.
  