| Plan Review Notes For Permit 03041708 |
| Permit Number |
03041708 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-19 00:00:00 | DENIED: | | | | | | 1.DUCT SMOKE DETECTORS SHALL BE R | | | INSTALLED IN THE SUPPLY AIR DUCT SYSTEMS | | | WITH THE DESIGN CAPACITY GREATER THAN | | | 2,000 CFM.2001 FBC(M) 606.2.1 | | | | | | 2.FAN SHUTDOWN BE DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM STROBE | | | IN NORMALLY OCCUPIED AREAS OR ACTIVATE | | | A VISIBLE & AUDIBLE SUPERVISORY SIGNAL | | | AT A CONSTANTLY ATTENDED LOCATION. | | | | | | 3.CONDENSATE SHALL TERMINATE A | | | MINIMUM OF 12" AWAY FROM THE BUILDING | | | STRUCTURE.2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|