| Plan Review Notes For Permit 03041708 |
| Permit Number |
03041708 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-22 00:00:00 | 1) PLEASE REF NFPA 101 LIFE SAFETY CODE | | | 2000 EDITION. | | | | | | 2) WET FIRE HYDRANTS SHALL BE INSTALLED | | | AND OPERATIONAL PRIOR TO AND DOING | | | CONSTRUCTION. ACCESS TO THESE FIRE | | | HYDRANTS MUST BE MAINTAINED THROUGHOUT | | | THE CONSTRUCTION. | | | | | | 3) SEPARATE PLANS AND PERMIT WILL BE | | | REQUIRED FOR INSTALLATION OF FIRE ALARM | | | AND FIRE SPRINKLER SYSTEM. | | | | | | 4) FAN SHUTDOWN DUCT SMOKE DETECTORS | | | SHALL BE INTERCONNECTED TO FIRE ALARM | | | SYSTEM. | | | | | | 5) FIRE DEPT CONNECTION SHALL BE 150 FT | | | OR LESS TO FIRE HYDRANT. | | | | | | 6) BUILDING SHALL HAVE APPROVED ADDRESS | | | NUMBERS PLACED IN A POSITION TO BE | | | PLAINLY LEGIBLE AND VISIBLE FROM THE | | | STREET AND ROAD FRONTING THE PROPERTY. | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|