| Plan Review Notes For Permit 03041708 |
| Permit Number |
03041708 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-08 00:00:00 | ************* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, #`ED | | | NOTES #5,7 MENTION EQUIPMENT GROUNDING | | | CONDUCTORS FROM GUTTER TO METER AND | | | METER TO MAIN DISC`S. THIS WOULD BE | | | PARALLELING THE NEUTRAL PER 250-24 | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ) 215-3/230-42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|