Plan Review Notes
Plan Review Notes For Permit 03041672
Permit Number 03041672
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* APPENDIX F102.2.4ROOF COVERING
 IN THE FIRE DISTRICT SHALL CONFORM TO
 THE REQUIREMENTS OF CLASS A OR B ROOF
 COVERINGS AS DEFINED IN FBC1505.PAGE 3
 OF THE SUBMITTED AEICOR PRODUCT APPROVAL
 NOA# 01-0820.01 GIVES THREE OPTIONS FOR
 THE FIRE BARRIER BOARD NECESSARY TO
 ACHIEVE CLASS A OR B FIRE RATING.NONE
 OF THESE OPTIONS HAVE BEEN SPECIFIED ON
 EITHER THE PLANS OR SECTION D OF THE
 SUBMITTED UNIFORM PERMIT APPLICATION.
 AMEND THE PLANS, AND THE UNIFORM PERMIT
 APPLICATION, TO SPECIFY FIRE BARRIER
 BOARD.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO