| Plan Review Notes For Permit 03041640 |
| Permit Number |
03041640 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-27 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE STORM SHUTTERS INFORMATION | | | WITH UPDATED SBCCI REPORT. | | | 2-REVISE DETAIL S21 FOR LOCATED BETWEEN | | | GARAGE AND STAIRWAY TO MATCH THOSE | | | CONDITIONS SHOWN ON 2ND FLOOR FRAMING | | | PLAN. SEC. 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | 3-WINDOW 34SH DOESN'T PROVIDE THE 24" | | | CLEAR HEIGHT REQUIRED BY SECTION | | | 1005.4 FBC 2001. REVISE AS REQUIRED. | | | 4-REVISE TRUSS ANCHOR SCHEDULE TO COMPLY | | | WITH SEC. 1609.4.3 FBC 2001, WHICH | | | DOESN'T ALLOW THE 33% ALLOWABLE STRESS | | | INCREASE TO BE USED. SEE USP 2003 | | | CATALOGUE FOR REVISED LOADS. |
|