2003-04-24 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 WIRING OF THE KITCHEN MUST COMPLY WITH
 THE FOLLOWING CODES.
  
 1} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 2} 250-140 FOR THE RANGE.
  
 3} 210-8(A)(6)_GFI PROTECTION.
  
 4} 220-16(A) RATING & NUMBER OF
 CIRCUITS.
  
 PLEASE CHECK THE APPLICABLE CODES AND
 REDRAW THE PLAN TO SHOW COMPLIANCE.
 THERE IS AN ELECTRICAL PERMIT REQUIRED
 FOR THIS WORK.THE ELECTRICAL CONTRACTOR
 SHALL SUBMIT CORRECTED DRAWINGS AT THE
 TIME OF APPLICATION FOR HIS PERMIT AS A
 REVISION TO THIS DRAWING.
  