2003-04-24 00:00:00DRYER ROOMS ARE CONFINED SPACES.
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 - 1,100 CU FT REQUIRED
 IN EACH. 1ST FLOOR PROVIDES 955 CU FT
 AND 2ND FLOOR PROVIDES 255 CU FT OR 803
 CU FT DEPENDING ON DOORS TO CLOSET AND
 CEILING HEIGHT, (CALCULATED AT 9'4")
 **SHUT OFF VALVES REQD. 409.7
 **SEDIMENT TRAPS REQD. 408.4