| Plan Review Notes For Permit 03041561 |
| Permit Number |
03041561 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-24 00:00:00 | DRYER ROOMS ARE CONFINED SPACES. | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2 - 1,100 CU FT REQUIRED | | | IN EACH. 1ST FLOOR PROVIDES 955 CU FT | | | AND 2ND FLOOR PROVIDES 255 CU FT OR 803 | | | CU FT DEPENDING ON DOORS TO CLOSET AND | | | CEILING HEIGHT, (CALCULATED AT 9'4") | | | **SHUT OFF VALVES REQD. 409.7 | | | **SEDIMENT TRAPS REQD. 408.4 |
|