| 2003-05-16 00:00:00 | ********CORRECTIONS********** |
| | |
| | 1.)A NOTICE OF COMMENCEMENT IS |
| | REQUIRED TO BE FILED WITH THE CLERK OF |
| | COURTS BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.CALL 233-5025 FOR MORE |
| | INFORMATION.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)WINDOW V REQUIRES SAFETY GLASS. |
| | REVISE BOTH THE FLOOR PLAN AND THE |
| | WINDOW SCHEDULE. |
| | |
| | 4.)THE WINDOW/SGD AND 'REPAIR |
| | MASONRY GAPS' DETAILS (A12) MUST COMPLY |
| | WITH FBC 1707.4.4.2. |
| | |
| | 5.)THE GARAGE DOOR ATTACHMENT DETAIL |
| | (A12) CONFLICTS WITH THE PRODUCT |
| | APPROVAL. |
| | |
| | 6.)THE ROOF SPECS AND SINGLE HUNG |
| | WINDOW PRODUCT APPROVALS ARE ILLEGIBLE. |
| | PROVIDE LEGIBLE COPIES. |
| | |
| | 7.)THE UPLIFT VALUES FOR SOME OF THE |
| | CONNECTORS ARE INCORRECT.REFER TO |
| | USP 2003 CATALOG. |
| | |
| | 8.)SPECIFY CEILING FINISH AT THE |
| | ENTRY, WITH ATTACHMENTS. |
| | |
| | 9.)PROVIDE A STAIR SECTION WITH |
| | FIREBLOCKING, FBC 2305.1.4. |
| | |
| | 10.) PROVIDE A STRUCTURAL PLAN FOR THE |
| | STAIRS INDICATING HOW STAIRS AND |
| | LANDING WILL BE SUPPORTED. |
| | |
| | 11.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 12.)WOOD BALCONY RAILING DETAIL (A12) |
| | TO COMPLY WITH FBC 1015.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |