| 2003-06-02 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SOIL BORING TEST REPORT AS |
| | REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| | |
| | 4) THE 7/8" STUCCO THICKNESS REQUIRED BY |
| | ASTM C 926 ON METAL LATH OVER PLYWOOD |
| | SHEATHING WAS CHANGED ON THE WRONG WALL |
| | SECTION ON SHEET A6. THE 5/8" STUCCO |
| | OVER CONCRETE BLOCK IS ACCEPTABLE. |
| | PLEASE CORRECT. |
| | |
| | 5) DETAIL 25 ON A8,WHICH IS SPECIFIED ON |
| | SHEETS A7 AND A9, FOR THE CONNECTION OF |
| | THE FLOOR GIRDER TO THE WOOD POST IN THE |
| | BEARING WALL IS NOT THE CORRECT DETAIL. |
| | |
| | 6) THE UPLIFT VALUES FOR THE CONNECTORS |
| | GIVEN IN DETAILS 24/A8, 29/A8, 32/A8 AND |
| | 36/A8 ARE NOT CORRECT. SEE 2003 USP |
| | CATALOG AND NOTES ON THE PLAN. |
| | |
| | 7) THE SECOND FLOOR BRACING PLAN ON A10 |
| | SPECIFIES TC-5 AND TC-6 CONNECTORS. |
| | THESE ARE NOT LISTED IN THE CONNECTOR |
| | SCHEDULE ON A9. PLEASE CORRECT. |
| | |
| | 8) DETAIL 5/A10 IS SPECIFIED ON SHEET |
| | A10. THERE AREN'T ANY DETAILS ON SHEET |
| | A10. |
| | |
| | SEE NOTATIONS ON THE REVIEWED PLANS. |
| | PLEASE RETURN OLD PAGES WITH THE NEW |
| | WHEN RESUBMITTING. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |