Plan Review Notes
Plan Review Notes For Permit 03041480
Permit Number 03041480
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT FOR REVIEW.
  
 1} THE #4 GEC IS INCORRECT FOR THE 400
 AMP SERVICE SHOWN.SHOULD BE 1/0 PER
 250-66.
  
 2} THE FEEDER TO PANEL "B" IS MISSING AN
 EQUIPMENT GROUND PER 250-122.
  
 3} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED @ 1500 VA PER 220-16(B).
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 DOES NOT COMPLY WITH 8-1.4.2
 NFPA-72.MUST BE A LISTED HEAT DETECTOR.
  
 6} THE SMOKE DETECTOR AT THE DOOR OF THE
 MASTER BEDROOM MUT BE IN THE VESTIBULE
 TO COMPLY WITH 8-1.4.1.6(2) NFPA-72.
  
 7} PANELS "A" & "B" ARE SHOWN AS 200 AMP
 & FED AS 200 AMP ON THE RISER,BUT LIST-
 ED AS 150 AMP ON THE SCHEDULES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718