2003-05-15 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
  
 4) THE PRIVACY WALL FOOTING AT THE ZERO
 LOT LINE ENCROACHES ON THE ADJACENT
 PROPERTY.
  
 5) THE FOUNDATION PLAN AND FLOOR PLAN
 SHEETS ARE NOT NUMBERED.
  
 6) THE FLOOR PLAN REFERENCES DETAIL 2 ON
 A3 FOR THE WOOD FRAME BEARING WALL. THE
 CORRECT DETAIL IS 3 ON A3.
  
 7) DETAIL 3 ON A3 REFRENCES THE SFBC.
 THE CURRENT CODE IS 2001 FBC.
  
 8) DETAIL 1 ON A3 SPECIFIES R-11
 INSULATION IN THE ATTIC. THE ENERGY
 CALCULATIONS REQUIRE R-19.
  
 9) SPECIFY ON THE PLANS THAT THE BALCONY
 GUARDRAILS ARE REQUIRED TO HAVE
 INTERMEDIATE RAILS THAT SPACED TO REJECT
 A 4"SPHERE AND A BOTTOM RAIL THAT WILL
 REJECT A 2"SPHERE. SUBMIT SHOP DRAWINGS.
 FBC 1015.3
  
 10) FIREBLOCKING IS REQUIRED AT THE
 CONCEALED SPACES BETWEEN STAIR STRINGERS
 AT THE TOP AND BOTTOM OF THE RUN PER
 FBC 2305.1.4.
  
 11) THE STUCCO ON METAL LATH AT THE
 EXTERIOR WALL SECTION ON A6 IS REQUIRED
 TO BE 7/8" THICK PER ASTM C 926.
  
 12) SPECIFY ON THE PLANS THAT ADEQUATE
 SUBSTRATE WILL BE PROVIDED AT GLAZED
 OPENINGS IN THE WOOD FRAME WALLS FOR THE
 ATTACHMENT OF STORM PANELS.
  
 13) DETAIL 12 ON A7 SPECIFIED ON SHEET
 A9 IS NOT THE CORRECT DETAIL FOR THE
 GIRDER TO WOOD BEARING WALL CONNECTION.
  
 14) THERE IS NO DETAIL 12 ON A8 AS
 SPECIFIED ON SHEET A9AT THE COVERED
 BALCONY.
  
 15) THE TRUSS CONNECTORS IN THE SCHEDULE
 ON A9, ARE ALL DESIGNED TO BE EMBEDDED
 IN CONCRETE. THESE ARE INCORRECTLY
 SPECIFIED AT THE WOOD FRAME WALLS AND
 WOOD GIRDERS AT THE BALCONY.
  
 16)THE CONNECTOR SCHEDULE ON A9 CONTAINS
 INCORRECT INFORMATION. THE MANUFACTURER
 DOES NOT ALLOW AN INCREASE IN THE LOAD
 VALUES BY ADDING MORE NAILS THAN
 SPECIFIED IN THE CATALOG. YOU ARE
 ALLOWED TO SPECIFY LESS NAILS AND REDUCE
 THE LOADS BASED ON SHEAR VALUES OF THE
 NAILS. THE VALUES LISTED IN THE SCHEDULE
 INCLUDE THE ONE THIRD INCREASE ON STEEL
 ALLOWABLE STRESS DESIGN VALUES WHICH IS
 NO LONGER ALLOWED BY FBC 1609.4.3. SEE
 2003 USP CATALOG.
  
 17) THE STORM PANEL INFORMATION IS
 INCORRECT. THE WRONG ANCHOR TYPE IS
 LISTED IN THE SCHEDULE FOR OPENINGS #12,
 13,14,15,18 AND 19, WHICH ARE IN WOOD
 FRAME WALLS. THE OPENINGS SIZES LISTED
 ARE INCORRECT FOR OPENINGS #14,18 & 19.
 THE ALLOWABLE PANEL SPANS ARE EXCEEDED
 AT SEVERAL OPENINGS BASED ON THE SPAN
 TABLES IN THE PRODUCT APPROVAL DRAWINGS.
 PLEASE CORRECT.
  
 18) SEE HANDWRITTEN NOTATIONS ON THE
 REVIEWED PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202