| Plan Review Notes For Permit 03041478 |
| Permit Number |
03041478 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-10-30 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS NOR DOES IT REFLECT | | | THE FLOOR PLAN. - THE SHOWER IN THE | | | MASTER BATH IS NOT VENTED, 901.2.1 | | | - SEE ORIGINAL SANT. RISER DIAGRAM | | | DATED 6-14-3. THAT RISER DIAGRAM MEETS | | | THE CODE REQUIREMENTS & REFLECTS THE | | | FLOOR PLAN. IF THE FLOOR PLAN HAS BEEN | | | CHANGED THEN A REVISION SHALL BE SUBMIT- | | | TED FOR THE FLOOR PLAN. IF THE FLOOR | | | PLAN IS REVISED, IT SHALL REFLECT THE | | | SANITARY RISER DIAGRAM. PLEASE CLAIRFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|