| 2003-05-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. THE SIZE OF THE | | | DRAINAGE PIPING SHALL NOT BE REDUCED IN | | | SIZE IN THE DIRECTION OF THE FLOW. SEC | | | 704.2. (BATH #2 THRU KIT) - TUB & SHOWER | | | IN MASTER BATH NOT VENTED.- FIXTURES | | | FROM LAUNDRY SHALL NOT DRAIN INTO THE | | | WET VENT FOR MASTER BATH. 909.1. - DOES | | | NOT REFLECT FLOOR PLAN. - SECOND FLOOR | | | BATHROOMS/LAUNDRY ROOM SHALL NOT DRAIN | | | THRU FIRST FLOOR POWDER ROOM PIPING. | | | ---SEE ATTACHED SHEET FOR EXAMPLE OF A | | | SAN. RISER DIAGRAM THAT REFLECTS THE | | | FLOOR PLAN AND MEETS CODE REQUIREMENTS.- | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|