2003-05-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. THE SIZE OF THE
 DRAINAGE PIPING SHALL NOT BE REDUCED IN
 SIZE IN THE DIRECTION OF THE FLOW. SEC
 704.2. (BATH #2 THRU KIT) - TUB & SHOWER
 IN MASTER BATH NOT VENTED.- FIXTURES
 FROM LAUNDRY SHALL NOT DRAIN INTO THE
 WET VENT FOR MASTER BATH. 909.1. - DOES
 NOT REFLECT FLOOR PLAN. - SECOND FLOOR
 BATHROOMS/LAUNDRY ROOM SHALL NOT DRAIN
 THRU FIRST FLOOR POWDER ROOM PIPING.
 ---SEE ATTACHED SHEET FOR EXAMPLE OF A
 SAN. RISER DIAGRAM THAT REFLECTS THE
 FLOOR PLAN AND MEETS CODE REQUIREMENTS.-
  
 REVIEW BY KEN STEVENS