Plan Review Notes
Plan Review Notes For Permit 03041478
Permit Number 03041478
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} THE #4 GEC IS INCORRECT FOR A 400 AMP
 SERVICE. SEE 250-66.
  
 2} THE FEEDER TO PANEL "B" MUST HAVE AN
 EQUIPMENT GROUND PER 250-122.
  
 3} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED AT 1500 VA PER 220-16-(B).
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 MUST BE REMOVED OR BE CHANGED TO A
 LISTED HEAT DETECTOR PER NFPA-72 ART
 8-1.4.2.
  
 6} THE SMOKE DETECTOR AT THE DOOR OF THE
 MASTER BEDROOM MUST BE IN THE VESTIBULE
 TO COMPLY WITH 8-1.4.1.6(2),(OUTSIDE).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718