| Plan Review Notes For Permit 03041478 |
| Permit Number |
03041478 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-24 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | TO THE PLAN AND RESUBMIT FOR REVIEW. | | | | | | 1} THE #4 GEC IS INCORRECT FOR A 400 AMP | | | SERVICE. SEE 250-66. | | | | | | 2} THE FEEDER TO PANEL "B" MUST HAVE AN | | | EQUIPMENT GROUND PER 250-122. | | | | | | 3} THE LAUNDRY CIRCUIT MUST BE | | | CALCULATED AT 1500 VA PER 220-16-(B). | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} THE SMOKE DETECTOR IN THE KITCHEN | | | MUST BE REMOVED OR BE CHANGED TO A | | | LISTED HEAT DETECTOR PER NFPA-72 ART | | | 8-1.4.2. | | | | | | 6} THE SMOKE DETECTOR AT THE DOOR OF THE | | | MASTER BEDROOM MUST BE IN THE VESTIBULE | | | TO COMPLY WITH 8-1.4.1.6(2),(OUTSIDE). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|