2003-05-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03041478
 ADD:6222 HAMMOCK PARK RD
 CONT: DOUBLE R BUILDERS
 TEL: (954)796-0777
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE: CONTRACTOR IS CONTINEUING AT OWN
 RISK!THE SOILS REPORT SUBMITTED TO
 THIS OFFICE NOT A SEALED COPY. THIS
 REPORT INDICATES THAT THIS IS A
 "PRELIMINARY GEOTECHNICAL EVALUATION,
 UNDER LIMITATIONS(5.0) IT IS IMPORTANT
 TO REALIZE THAT THE INFORMATION PROVIDED
 IN THIS REPORT IS NOT SUFFICIENT FORA
 FINAL DESIGN OF THE FOUNDATION SYSTEM".
 RENAISSANCE SECTION # 7.
  
 2) SHEET A-1:
 A) DETAILA: PRIVACY WALL IS INDICATED
 ON ZERO-LOT LINE SIDE, FOOTER OVER PROP-
 ERTY LINE.
 B) DETAIL # 38 INDICATES THE FOUNDA-
 TION IS ONLY 8" BELOW GRADE.
 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 3) SHEET A-3 EGRESS WINDOWS IN THE BED-
 ROOM # 3 & BEDROOM # 5, DO NOT MEET THE
 HEIGHT REQUIREMENT.
 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
 LAWSON SH 34+4 = THE CLEAR HEIGHT IN A
 34 IS 20.09" ADD 1/2 0F 4"=22.09 NOT THE
 REQUIRED 24" MINIMUM.
  
 4) SHEET A-4 GUARDRAILS, REAR ELEVATION,
 MAXIMUM BETWEEN THE DECK AND BOTTOM RAIL
 IS 2".
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 5) SHEET A-5 JAMB/ HEAD WINDOW BUCKS
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 *****USP 2003 CATALOG******
 SHEET A-8 USP RT18 & RT22 HIGH VALUES
 SHEET A-9 TA-12R 895
 TA-14R 1205
 TA-16R 1205
  
 RE-EVALUATE DETAILS (STRAPS) WITH NO
 LOADS INDICATED.
 SHEET A-8& A-9 RE-EVALUATE TRUSS PLAN
 LAYOUT MARKINGS WITH THE NEW LOWER
 VALUES REQUIRED BY THE 2001 FL CODE.
  
 7) MISSING THE INTERNAL PRESSURE COEFFIC
 IENT FOR ENCLOSED BUILDINGS. -.18
 C-1 WIND DESIGN UNDER LOAD SCHEDULE.
  
 MISSING OPENING PRESSURES, POSITIVE/
 NGATIVE.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW