| Plan Review Notes For Permit 03041477 |
| Permit Number |
03041477 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-07-14 00:00:00 | ************ UNSAT ************* | | | | | | 1)NOTE: PLEASE REMOVE EQUIPMENT GROUND- | | | -ING CONDUCTOR FROM METER TO PANEL W/ | | | MCB. PLANS USED TO SHOW A MAIN DISC ON | | | THE LINE SIDE OF PANEL AND THEREFORE AN | | | EQUIPMENT GRND IS REQ`D. HOWEVER, THERE | | | IS NO MAIN SHOWN ANYMORE. 250-24 | | | | | | 2)NOTE: PLEASE PLACE REQ'D INFORMATION | | | UNDER FAC/ FS ON TITLE BLOCK. LICENSE # | | | FIRM REG #. 61G1-16.004, 481 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|