2003-07-14 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE REMOVE EQUIPMENT GROUND-
 -ING CONDUCTOR FROM METER TO PANEL W/
 MCB. PLANS USED TO SHOW A MAIN DISC ON
 THE LINE SIDE OF PANEL AND THEREFORE AN
 EQUIPMENT GRND IS REQ`D. HOWEVER, THERE
 IS NO MAIN SHOWN ANYMORE. 250-24
  
 2)NOTE: PLEASE PLACE REQ'D INFORMATION
 UNDER FAC/ FS ON TITLE BLOCK. LICENSE #
 FIRM REG #. 61G1-16.004, 481
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]