| 2003-05-16 00:00:00 | *********CORRECTIONS******** |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.233-5025 |
| | |
| | 3.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 4.)THE GARAGE DOOR JAMB DETAIL |
| | CONFLICTS WITH THE PRODUCT APPROVAL(A8). |
| | |
| | 5.)'REPAIR MASONRY GAPS' AND 'WINDOW |
| | & SGD' DETAILS MUST COMPLY WITH FBC |
| | 1707.4.4.2. |
| | |
| | 6.)SOME OF THE CONNECTOR VALUES ARE |
| | INCORRECT.REFER TO USP 2003 CATALOG. |
| | |
| | 7.)THE PRIVACY WALL DETAIL, SHEET A7, |
| | CONFLICTS WITH THE PRIVACY WALL DETAIL, |
| | SHEET A3. |
| | |
| | 8.)SHOW WINDOW O AS TEMPERED ON THE |
| | WINDOW SCHEDULE. |
| | |
| | 9.)SINGLE HUNG WINDOW AND ROOF SPECS |
| | ARE ILLEGIBLE. |
| | |
| | 10.) THE SITE SPECIFIC MUST BE SEALED BY |
| | THE ENGINEER IN SECTION 9. |
| | |
| | 11.)THE STORM PANELS FOR OPENINGS |
| | #7 AND #10 EXCEED THE SPAN ALLOWED PER |
| | SBCCI PRODUCT APPROVAL.#12 HAS |
| | INCORRECT ANCHOR SPACING. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |