Plan Review Notes
Plan Review Notes For Permit 03041477
Permit Number 03041477
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-16 00:00:00*********CORRECTIONS********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.233-5025
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 4.)THE GARAGE DOOR JAMB DETAIL
 CONFLICTS WITH THE PRODUCT APPROVAL(A8).
  
 5.)'REPAIR MASONRY GAPS' AND 'WINDOW
 & SGD' DETAILS MUST COMPLY WITH FBC
 1707.4.4.2.
  
 6.)SOME OF THE CONNECTOR VALUES ARE
 INCORRECT.REFER TO USP 2003 CATALOG.
  
 7.)THE PRIVACY WALL DETAIL, SHEET A7,
 CONFLICTS WITH THE PRIVACY WALL DETAIL,
 SHEET A3.
  
 8.)SHOW WINDOW O AS TEMPERED ON THE
 WINDOW SCHEDULE.
  
 9.)SINGLE HUNG WINDOW AND ROOF SPECS
 ARE ILLEGIBLE.
  
 10.) THE SITE SPECIFIC MUST BE SEALED BY
 THE ENGINEER IN SECTION 9.
  
 11.)THE STORM PANELS FOR OPENINGS
 #7 AND #10 EXCEED THE SPAN ALLOWED PER
 SBCCI PRODUCT APPROVAL.#12 HAS
 INCORRECT ANCHOR SPACING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]