| Plan Review Notes For Permit 03041476 |
| Permit Number |
03041476 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-27 00:00:00 | | | | FAILED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RISER DIAGRAM AND THE PANEL | | | SCHEDULE FEEDER SIZE FOR SUB PANEL DO | | | NOT CORRELATE.SEE 1-15 #14 ON SCHEDULE | | | & 3 #6'S ON RISER. | | | | | | 2} REVISION #3 SHOWS THE ADDITION OF | | | AN"INSTA HOT",BUT THE ADDED LOAD DOES | | | NOT APPEAR ON THE SCHEDULE. | | | | | | 3} PLEASE RECALCULATE THE TOTAL LOAD. | | | 45.7 DOES NOT SEEM TO BE CORRECT. | | | | | | 4} THE TITLE BLOCK DOES NOT CONTAIN THE | | | FIRM LICENSE NUMBER PER 61G1-16.004(2). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|