| 2003-05-15 00:00:00 | **********CORRECTIONS*********** |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY; CALL 233-5025 FOR MORE |
| | INFORMATION.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)THE COLUMN LEGEND ON SHEET A3 IS |
| | PARTIALLY ILLEGIBLE. |
| | |
| | 4.)SHOW WINDOWS BB AND U AS TEMPERED |
| | ON THE FLOOR PLAN, SHEET A6. |
| | |
| | 5.)SHOW WINDOWS Q AND R AS TEMPERED |
| | ON THE WINDOW SCHEDULE, A1. |
| | |
| | 6.)THE WINDOW AND SGD JAMB DETAIL, |
| | AND THE 'REPAIR MASONRY GAPS' DETAIL, |
| | SHEET A12, MUST COMPLY WITH FBC |
| | 1707.4.4.2. |
| | |
| | 7.)SOME VALUES FOR THE USP CONNECTORS |
| | ARE INCORRECT (SHEET A8).REFER TO |
| | THE 2003 CATALOG. |
| | |
| | 8.)PROVIDE LEGIBLE PRODUCT APPROVALS |
| | (SINGLE HUNG WINDOW, TILE SPECS). |
| | |
| | 9.)SOME PANEL LENGTHS ON THE |
| | HURRICANE SHUTTER INSTALLATION SCHEDULE |
| | EXCEED THE MAX LENGTH FOR THE DESIGN |
| | PRESSURE INDICATED.REVISE. |
| | |
| | 10.)SHEET A5, BEARING WALL NOTE IS |
| | ILLEGIBLE. |
| | |
| | 11.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |