2003-05-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. THE SIZE OF THE
 DRAINAGE PIPING SHALL NOT BE REDUCED IN
 SIZE IN THE DIRECTION OF THE FLOW. SEC
 704.2. (BATH #2 THRU KIT) - TUB & SHOWER
 IN MASTER BATH NOT VENTED. - FIXTURES
 FROM LAUNDRY ROOM SHALL NOT DRAIN INTO
 THE WET VENT FOR MASTER BATH. - DOUBLE
 SANITARY TEE PATTERNS SHALL NOT REVIEVE
 THE DISCHARGE OF FIXTURES OR APPLIANCES
 WITH PUMPING ACTION DISCHARGE. (WASH
 MACHINE) 706.3 - DOES NOT REFLECT FLOOR
 PLAN. - SECOND FLOOR BATHROOMS AND LAUN-
 DRY ROOM SHALL NOT DRAIN THRU FIRST
 FLOOR PIPING OF THE POWDER ROOM.
 -----SEE ATTACHED SHEET THAT REFLECTS
 THE FLOOR PLAN AND MEETS ALL CODE RE-
 QUIREMENTS. ------------
  