| Plan Review Notes For Permit 03041475 |
| Permit Number |
03041475 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. THE SIZE OF THE | | | DRAINAGE PIPING SHALL NOT BE REDUCED IN | | | SIZE IN THE DIRECTION OF THE FLOW. SEC | | | 704.2. (BATH #2 THRU KIT) - TUB & SHOWER | | | IN MASTER BATH NOT VENTED. - FIXTURES | | | FROM LAUNDRY ROOM SHALL NOT DRAIN INTO | | | THE WET VENT FOR MASTER BATH. - DOUBLE | | | SANITARY TEE PATTERNS SHALL NOT REVIEVE | | | THE DISCHARGE OF FIXTURES OR APPLIANCES | | | WITH PUMPING ACTION DISCHARGE. (WASH | | | MACHINE) 706.3 - DOES NOT REFLECT FLOOR | | | PLAN. - SECOND FLOOR BATHROOMS AND LAUN- | | | DRY ROOM SHALL NOT DRAIN THRU FIRST | | | FLOOR PIPING OF THE POWDER ROOM. | | | -----SEE ATTACHED SHEET THAT REFLECTS | | | THE FLOOR PLAN AND MEETS ALL CODE RE- | | | QUIREMENTS. ------------ | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|