2003-05-19 00:00:00*********CORRECTIONS*********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 4.)PRIVACY WALL DETAIL A-A1 ENCROACHES
 THE PROPERTY LINE.
  
 5.)PROVIDE DOCUMENTATION FOR THE
 "34+4" SINGLE HUNG EGRESS WINDOW.SHOW
 CLEAR NET OPENING FROM THE MANUFACTURER;
 FBC 1005.4.
  
 6.)THE JAMB DETAIL FOR THE GARAGE
 DOOR CONFLICTS WITH THE ATTACHMENTS
 SPECIFIED ON THE PRODUCT APPROVAL.
  
 7.)PROVIDE LEGIBLE PRODUCT APPROVALS
 AND SPECS.
  
 8.)THE WINDOW AND DOOR DETAILS ARE TO
 COMPLY WITH 1707.4.4.2.
  
 9.)WATERSTOP REQUIRED PER CITY OF WPB
 AMENDMENTS TO THE FBC, 2111.1.9.REVISE
 THE FRENCH DOOR DETAIL AND THE TYPICAL
 WALL SECTION.
  
 10.)SECTION 3-A3 REFERS TO SFBC.
 CURRENT CODE IS FBC 2001.
  
 11.)FLOOR PLAN REFERS TO 2-A3.THIS
 SHOULD BE 3-A3.
  
 12.)INSULATION FOR DETAIL 3-A3 IS R11,
 ENERGY CALCS SPECIFY R19 (CEILING).
 SHOW WALL INSULATION AND FIRESTOP.
  
 13.)DETAIL 1-A3 SHOWS R11 INSULATION,
 ENERGY CALCS SPECIFY R19.
  
 14.)DETAIL 38-A1; 8" MIN. BELOW GRADE
 SHOULD BE 12" MIN, FBC 1804.1.3.
  
 15.)THE HURRICANE SHUTTER SCHEDULE
 HAS AN ANCHOR FOR CONCRETE; A5 WINDOW
 DETAILS SHOW WOOD.CLARIFY.
  
 16.)THE UPLIFT VALUES FOR THE
 CONNECTORS ARE INCORRECT; REFER TO THE
 USP 2003 CATALOG.