| Date |
Text |
| 2003-05-19 00:00:00 | *********CORRECTIONS********* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 3.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 4.)PRIVACY WALL DETAIL A-A1 ENCROACHES |
| | THE PROPERTY LINE. |
| | |
| | 5.)PROVIDE DOCUMENTATION FOR THE |
| | "34+4" SINGLE HUNG EGRESS WINDOW.SHOW |
| | CLEAR NET OPENING FROM THE MANUFACTURER; |
| | FBC 1005.4. |
| | |
| | 6.)THE JAMB DETAIL FOR THE GARAGE |
| | DOOR CONFLICTS WITH THE ATTACHMENTS |
| | SPECIFIED ON THE PRODUCT APPROVAL. |
| | |
| | 7.)PROVIDE LEGIBLE PRODUCT APPROVALS |
| | AND SPECS. |
| | |
| | 8.)THE WINDOW AND DOOR DETAILS ARE TO |
| | COMPLY WITH 1707.4.4.2. |
| | |
| | 9.)WATERSTOP REQUIRED PER CITY OF WPB |
| | AMENDMENTS TO THE FBC, 2111.1.9.REVISE |
| | THE FRENCH DOOR DETAIL AND THE TYPICAL |
| | WALL SECTION. |
| | |
| | 10.)SECTION 3-A3 REFERS TO SFBC. |
| | CURRENT CODE IS FBC 2001. |
| | |
| | 11.)FLOOR PLAN REFERS TO 2-A3.THIS |
| | SHOULD BE 3-A3. |
| | |
| | 12.)INSULATION FOR DETAIL 3-A3 IS R11, |
| | ENERGY CALCS SPECIFY R19 (CEILING). |
| | SHOW WALL INSULATION AND FIRESTOP. |
| | |
| | 13.)DETAIL 1-A3 SHOWS R11 INSULATION, |
| | ENERGY CALCS SPECIFY R19. |
| | |
| | 14.)DETAIL 38-A1; 8" MIN. BELOW GRADE |
| | SHOULD BE 12" MIN, FBC 1804.1.3. |
| | |
| | 15.)THE HURRICANE SHUTTER SCHEDULE |
| | HAS AN ANCHOR FOR CONCRETE; A5 WINDOW |
| | DETAILS SHOW WOOD.CLARIFY. |
| | |
| | 16.)THE UPLIFT VALUES FOR THE |
| | CONNECTORS ARE INCORRECT; REFER TO THE |
| | USP 2003 CATALOG. |