| Plan Review Notes For Permit 03041474 |
| Permit Number |
03041474 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. THE SIZE OF THE | | | DRAINAGE PIPING SHALL NOT BE REDUCEN IN | | | SIZE IN THE DIRECTION OF THE FLOW. SEC | | | 704.2 (BATH #2 THRU KIT) - TUB & SHOWER | | | NOT VENTED IN MASTER BATH. - FIXTURES | | | FROM LAUNDRY SHALL NOT DRAIN INTO THE | | | WET VENT FOR MASTER BATH. 909.1 - DOES | | | NOT REFLECT THE FLOOR PLAN. - SECOND FLR | | | BATHROOMS/LAUNDRY ROOM SHALL NOT DRAIN | | | THRU POWDER ROOM PIPING FIRST FLOOR. - | | | --- SEE ATTACHED SHEET FOR EXAMPLE OF A | | | SANT. RISER DIAG. THAT REFLECTS FLOOR | | | PLAN AND MEETS CODE REQUIREMENTS.--- | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|