Plan Review Notes
Plan Review Notes For Permit 03041474
Permit Number 03041474
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN.
 2) 909.1 WASH MACHINE AND LAUNDRY SINK
 SHALL NOT DRAIN THROUGHT THE WET VENTED
 HORIZONTAL DRAIN OF THE MASTER BATH.
 LAUNDRY FIXTURES SHALL ENTER DRAIN DOWN-
 STREAM OF WET VENTED BATHROOM GROUP.
 3) TOO MANY LAVS FOR MASTER BATH SHOWN
 ON RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692