| Plan Review Notes For Permit 03041473 |
| Permit Number |
03041473 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-06 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE CORRECT THE FOLLOWING AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} THE ELECTRICAL SUB PANEL IS SHOWN AS | | | MLO BUT THERE IS NO BREAKER FOR IT | | | LISTED IN THE MAIN PANEL.SEE 230-71. | | | | | | 2} THE METER LOCATION APPEARS TO BE IN | | | VIOLATION OF 110-26 IN RELATION TO THE | | | A/C UNITS. | | | | | | 3} THE SMOKE DETECTORS IN AND OUT OF | | | BEDROOM #5 DO NOT COMPLY WITH 8-1.4.2. |
|