Plan Review Notes
Plan Review Notes For Permit 03041473
Permit Number 03041473
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} THE ELECTRICAL SUB PANEL IS SHOWN AS
 MLO BUT THERE IS NO BREAKER FOR IT
 LISTED IN THE MAIN PANEL.SEE 230-71.
  
 2} THE METER LOCATION APPEARS TO BE IN
 VIOLATION OF 110-26 IN RELATION TO THE
 A/C UNITS.
  
 3} THE SMOKE DETECTORS IN AND OUT OF
 BEDROOM #5 DO NOT COMPLY WITH 8-1.4.2.